Diagnostics Via Leds - Siemens SINAMICS S150 NEMA Operating Instructions Manual

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Diagnostics / faults and alarms
10.2 Diagnostics
10.2
Diagnostics
Description
This section describes procedures for identifying the causes of problems and the measures
you need to take to rectify them.
Note
Errors or malfunctions
If errors or malfunctions occur in the device, you must carefully check the possible causes
and take the necessary steps to rectify them. If you cannot identify the cause of the problem
or you discover that components are defective, your regional office or sales office should
contact Siemens Service and describe the problem in more detail. Addresses of contact
persons are listed in the preface.
10.2.1

Diagnostics via LEDs

Control Unit (-A10)
Table 10- 1
Description of the LEDs on the CU320-2 DP Control Unit
LED
Color
RDY (READY)
---
Green
Red
Red/green
Orange
Green/
orange or
red/orange
718
State
Description
OFF
The electronic power supply is missing or lies outside the
permissible tolerance range.
Continuous light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
0.5 Hz flashing
Commissioning/reset
light
2 Hz flashing light
Writing to the memory card.
Flashing light -
PROFIenergy energy saving mode is active (in conjunction with
0.5 s on 3 s off
option G33 - CBE20)
2 Hz flashing light
General fault
0.5 Hz flashing
Control Unit is ready for operation.
light
However, there are no software licenses.
0.5 Hz flashing
Firmware update in progress for the connected DRIVE-CLiQ
light
components.
2 Hz flashing light
Firmware update of components has been completed. Wait for
POWER ON of the respective component.
2 Hz flashing light
Component detection via LED is activated (p0124[0]).
Note:
Both options depend on the LED status when component
recognition is activated using p0124[0] = 1.
Operating Instructions, 12/2018, A5E36652151A