Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
7.4.3.4

Speed controller adaptation

Description
Two adaptation methods are available, namely free Kp_n adaptation and speed-dependent
Kp_n/Tn_n adaptation.
Free Kp_n adaptation is also active in "operation without encoder" mode and is used in
"operation with encoder" mode as an additional factor for speed-dependent Kp_n adaptation.
Speed-dependent Kp_n/Tn_n adaptation is only active in "operation with encoder" mode and
also affects the Tn_n value.
Figure 7-13
A dynamic response reduction in the field-weakening range can be activated in encoderless
operation (p1400.0). This is activated when the speed controller is optimized in order to
achieve a greater dynamic response in the base speed range.
Example of speed-dependent adaptation
Note
This type of adaptation is only active in "operation with encoder" mode.
284
p 1459
p 1455
x
( 0 )
p 1458
p 1456
p 1466
( 1 )
p 1460
0
p 1470
1
p 1461
p1465
p1464
p 1463
p 1462
0
p 1472
1
Free Kp adaptation
1
y
x
p 1457
p1400.6
0
1
p1400.5
0
1
p1400.0
1
0
1
p1400.5
1
0
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A