Functions, monitoring and protective functions
9.3 Drive functions
Notes on setting the release (opening) time (p1216):
● The release time (p1216) should be set longer than the actual release time of the holding
brake. As a result, the drive will not accelerate when the brake is closed.
Notes on setting the closing time (p1217):
● The closing time (p1217) should be set longer than the actual closing time of the holding
brake. As a result, the pulses are suppressed only after the holding brake is closed.
● If the closing time (p1217) is set too low compared to the actual closing time of the
holding brake, the load may drop suddenly.
● If the closing time (p1217) is set too high compared to the actual closing time of the
holding brake, the controller acts against the holding brake and thus reduces its service
life.
Function diagram
FP 2701
Parameters
• r0056.4
• r0060
• r0063[0...2]
• r0108.14
• p0855[C]
• p0856
• p0858
• r0899.12
• r0899.13
• p1215
• p1216
• p1217
• p1226
• p1227
• p1228
• p1278
558
Simple brake control (r0108.14 = 0)
Magnetizing completed
CO: Speed setpoint before the setpoint filter
CO: Actual speed value
Extended brake control
BI: Unconditionally release holding brake
BI: Speed controller enabled
BI: Unconditionally apply holding brake
BO: Holding brake open
BO: Command, close holding brake
Motor holding brake configuration
Motor holding brake release time
Motor holding brake closing time
Threshold for standstill detection
Standstill detection monitoring time
Pulse suppression delay time
Brake control diagnostic evaluation
Operating Instructions, 12/2018, A5E36652151A