Step 3 Start the UPS in normal mode using one of the following methods.
----End

6.2.1.4 Powering On Loads

Procedure
Step 1 When the UPS runs properly, switch on the UPS AC output circuit breaker Q1 and
rPDU (optional) switch to supply power to loads.
----End

6.2.1.5 Shutting Down the UPS

Shutting Down the Inverter to Transfer the UPS to Bypass Mode
Step 1 Shut down the UPS using one of the following methods. After you shut down a
UPS in the parallel system, the UPS has no output, and another UPS continues to
work.
Issue 03 (2023-08-20)
Method 1: When the UPS works in bypass mode, hold down the button on
the UPS panel for more than 5s. Release the button when the inverter
indicator blinks and you hear a beep sound. Do not press any button during
inverter startup. When the startup command is successfully delivered, and the
inverter indicator is steady on, the UPS enters normal mode.
Figure 6-12 Button position
Method 2: In bypass mode, choose Config > Control > Power-on/off on the
app to start the UPS. After successful startup, the UPS enters normal mode.
Method 3: On the WebUI, choose Monitoring > UPS > Running Control to
start the UPS.
NO TE
● Method 3 is used only when the SNMP card is configured.
● For details about how to start the UPS on the WebUI, see the
User Manual .
NO TE
To prevent triggering overload protection, start the loads with higher power and then loads
with lower power.
Method 1: When the UPS works in bypass mode, hold down the button on
the UPS panel for more than 5s. Release the button when the inverter