Starting The Inverter; Powering On Loads - Huawei UPS5000-E User Manual

Integrated ups 3.0
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Step 4 If the system has connected to the remote EPO switch, choose System Info. >
Settings > System Settings and set EPO detection to Enable.
Step 5 View the system running status diagram on the LCD to check that the UPS is
working in bypass mode.
----End

6.3.3 Starting the Inverter

UPS System User List
Table 6-4 UPS system user list
Default User
admin (administrator)
operator (common user)
Starting the Inverter on the LCD
Step 1 Choose Common Functions > Inv. ON.
Step 2 In the displayed login screen, select a user name and enter the password.
Step 3 In the displayed dialog box, tap Yes to start the inverter.
----End

6.3.4 Powering On Loads

After the inverter starts, the UPS works in normal mode. The Bypass mode alarm
disappears. Check that the UPS has transferred to normal mode by viewing the
system running status diagram.
Procedure
Step 1 After confirming that the battery strings are properly connected, turn on the
battery string input switch. If there are multiple battery strings, turn on the switch
Issue 06 (2023-08-25)
NO TE
● After you set parameters on the Settings Wizard screen, choose System Info > Settings
> System Settings. Check that Requisite modules and Redundant modules match the
actual values.
● If dry contact signals are connected to the system, choose System Info > Settings > Dry
Contact Set. Check that the connected dry contacts have been enabled and that the
disconnected dry contacts have been disabled.
NO TE
You can also start the inverter by choosing System Info > Maintenance > Inv. ON.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Preset Password
000001
000001
6 Power-On and Commissioning
Permission Description
Can set all the menus.
Can only view
parameters and set some
parameters.
172