NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Information
The reaction time of a digital signal is approx. 4-5 ms and consists of the following:
For digital inputs DIN2 and DIN3 there is a parallel channel which relays the signal pulses between 250 Hz and
205 kHz directly to the processor, and therefore makes it possible for a rotary encoder to be evaluated.
Pos : 160 /Anleitungen/El ektr oni k/FU und Starter/1. Allgemei nes /Sic herheits- und Ins tall ations hinweis e und Warn- Gefahrenhinweise/neu/War n- und Gefahrenhinweise/Informati on - Kabelführung @ 7\mod_1434636821334_14638.doc x @ 227205 @ @ 1
Information
All control cables (including PTC thermistors) must be routed separately from power and motor cables to prevent
interference in the device.
If the cables are routed in parallel, keep a minimum distance of 20 cm from cables which carry a voltage of >
60 V. The minimum distance may be reduced by shielding live cables or by using grounded metal separator
within the cable ducts.
Alternatively: Use of a hybrid cable with shielded control lines.