NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Starting the copy function
To start the copy function, set DIP switch S1-6 "COPY" from position { 0 } (factory setting) to position
{ 1 }. A 0  1 flank is detected here and the copying process is started at the next start of the variable
frequency drive.
1 Set DIP switch S1-6 "COPY" to { 1 },
2 Switch on the variable frequency drive ("POWER ON" (24 V)).
3  The copying process starts.
The copying process is not restarted without a previous change to the DIP switch.
Carry out the following steps to trigger the process again:
1 Set DIP switch S1-6 "COPY" to { 0 },
2 Switch on the variable frequency drive ("POWER ON" (24 V)),
3 Switch off the variable frequency drive ("POWER OFF" (24 V)),
4 Set DIP switch S1-6 "COPY" to { 1 },
5 Switch on the variable frequency drive ("POWER ON" (24 V)).
6  The copying process starts.
Information
The COPY function of DIP switch S1-6 "COPY" is comparable to parameter function P550 ("EEPROM copy
order" setting { 1 } "Ext.  Int. EEPROM"). This function is still available.
Pos : 247 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265496 @ @ 1
112
Parameter P550
BU 0200 en-US-3118