NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 444 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P400- P499/Parameter P418 – Funktion Analog ausg ang [SK 1x0E, SK 2xxE, SK 2xxE-FD S] @ 2\mod_1346931803196_14638.doc x @ 42643 @ @ 1
P418
[-01]
Analog output func.
...
(analog output function)
[-02]
0 ... 60
[-01] = IOE-1, AOUT of the first I/O extension (SK xU4-IOE)
{ all 0 }
[-02] = IOE-2, AOUT of the second I/O extension (SK xU4-IOE)
... only with
Analog functions (max. load: 5 mA analog):
SK CU4-IOE or
An analog voltage (0 ... +10 V) can be obtained from the control terminals (max. 5 mA). Various
SK TU4-IOE
functions are available, whereby:
0 Volt analog voltage always corresponds to 0% of the selected value.
10 V always corresponds to the rated motor value (unless otherwise stated) multiplied by the
P419 standardization factor, e.g.:
For standardization of actual values: ( Section 8.9 "Standardization of setpoint/target values").
10 = Torque [%]: the actual torque calculated by the VFD (100%=rated motor torque).
11 = Field [%] *, the actual field in the motor calculated by the VFD.
12 = Actual frequency ± *, the analog voltage is proportional to the output frequency of the
13 = Actual speed ± *, is the synchronous rotation speed calculated by the VFD, based on the
14 = Torque [%] ± *, is the actual torque calculated by the VFD, whereby the zero point is
29 = reserved for Posicon, see
174
0 = No function, no output signal at the terminals.
1 = Actual frequency *, the analog voltage is proportional to the VFD output frequency.
(100%=(P201))
2 = Actual speed *, this is the synchronous speed calculated by the VFD based on the
existing setpoint. Load-dependent speed fluctuations are not taken into account.
If servo mode is used, the measured speed will be output via this function.
(100%=(P202))
3 = Current *, the effective value of the output current supplied by the VFD. (100%=(P203))
4 = Torque current *, displays the motor load torque calculated by the VFD. (100 % =
(P112))
5 = Voltage *, the output voltage supplied by the VFD. (100%=(P204))
6 = D.c. link voltage, „DC link voltage", the DC voltage in the VFD. This is not based on the
rated motor data. 10 V with 100% standardization corresponds to 450 V DC (230 V line
power) or 850 V DC (480 V line power)!
7 = Value of P542, the analog output can be set using parameter P542 independently of the
actual operating status of the VFD. For example, with bus switching (parameter
command) this function can supply an analog value from the VFD, which is triggered by
the control unit.
8 = Apparent power *, the actual apparent power of the motor as calculated by the VFD.
(100 %=(P203)*(P204) or = (P203)*(P204)*√3)
9 = Real power*, the actual effective power calculated by the VFD.
(100 %=(P203)*(P204)*(P206) or = (P203)*(P204)*(P206)*√3)
VFD, whereby the zero point is shifted to 5 V. For rotation to the right, values between 5 V
and 10 V are output, and for rotation to the left values between 5 V and 0 V.
current setpoint, where the zero point has been shifted to 5 V. Values of 5 V to 10 V are
output with right-hand rotation, and values of 5 V to 0 V with left-hand rotation.
The measured speed is output via this function if servo mode is used.
shifted to 5 V. For drive torques, values between 5 V and 10 V are output, and for
generator torque, values between 5 V and 0 V.
rated motor value · P419
⇒ 10 Volt =
100%
BU0210
S
P
BU 0200 en-US-3118