E010
10.0
Bus timeout
10.2
Bus timeout option
10.4
Init error option
10.1
System error option
10.3
10.5
10.6
10.7
10.9
Module missing/P120
Pos : 659 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0200 en-US-3118
6 Operating status messages
(Telegram timeout/bus off 24 V int. CANbus
•
Data transfer is faulty. Check P513.
•
Check physical bus connections
•
Check bus protocol program process.
•
Check bus master.
•
Check 24 V supply of internal CAN/CANopen bus.
•
Node guarding error (internal CANopen)
•
Bus off error (internal CANbus)
Telegram timeout
•
Telegram transfer is faulty.
•
Check physical bus connections
•
Check bus protocol program process.
•
Check bus master.
•
PLC is in the "STOP" or "ERROR" state.
Initialization error in bus module
•
Check bus module current supply.
•
DIP switch setting of a connected I/O extension
module is incorrect
System error bus module
•
Further details can be found in the respective
additional bus instructions.
I/O extension:
Incorrect measurement of the input voltage or undefined
provision of the output voltage due to error in
reference voltage generation.
•
Short circuit at analog output
The module entered in parameter (P120) is not available.
•
Check connections