NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 506 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Parameter P523 – Wer ks einstellung [SK 1x0E, SK 2xxE] @ 2\mod_1346932168437_14638.doc x @ 43196 @ @ 1
Factory setting
P523
(factory setting)
0 ... 3
By selecting the appropriate value and confirming it with the Enter key, the selected parameter
range is entered in the factory setting. Once the setting has been made, the value of the
{ 0 }
parameter automatically returns to 0.
Pos : 507 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Parameter P523 – Wer ks einstellung_Ergänz ung [SK 2xxE] @ 9\mod_1448294698250_14638.doc x @ 266034 @ @ 1
Note: If an external EEPROM ("memory module") is plugged in, then a value of ("Factory setting
...") only affect this. If no "memory module" is present, the set command ("Factory setting ...") is
applied to the internal EEPROM
Pos : 508 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Parameter P525 – Lastüber wac hung Maxi mal wer t @ 0\mod_1328093087228_14638.doc x @ 15065 @ @ 1
P525
[-01]
Load control max.
...
(load monitoring, maximum value)
[-03]
1 ... 400%/401
Selection of up to 3 auxiliary values:
{ all 401 }
[-01] = Auxiliary value 1
Maximum load torque value.
Setting of the upper limit of load monitoring. Up to 3 values can be specified. Prefixes are not
taken into account, only the integer values are processed (motor/generator torque, right/left
rotation). The array elements [-01], [-02] and [-03] of parameters (P525) ... (P527), or the entries
which are made there always belong together.
401 = OFF Means that the function is switched off. No monitoring is performed. This is also the
basic setting for the VFD.
Pos : 509 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P500- P599/Parameter P526 – Lastüber wac hung Mini mal wert @ 0\mod_1328093137197_14638.doc x @ 15066 @ @ 1
P526
[-01]
Load control min.
...
(load monitoring, minimum value)
[-03]
0 ... 400 %
Selection of up to 3 auxiliary values:
{ all 0 }
[-01] = Auxiliary value 1
Minimum load torque.
Setting of the lower limit of load monitoring. Up to 3 values can be specified. Prefixes are not
taken into account, only the integer values are processed (motor/generator torque, right/left
rotation). The array elements [-01], [-02] and [-03] of parameters (P525) ... (P527), or the entries
which are made there always belong together.
0 = OFF
basic setting for the VFD.
Pos : 510 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265496 @ @ 1
194
0 = No change: Does not change the parameterization.
1 = Load factory setting: The complete parameterization of the VFD reverts to the factory
setting. All originally parameterized data are lost.
2 = Factory setting without bus: All parameters of the variable frequency drive, with the
exception of the bus parameter, are reset to the factory setting.
3 = Factory settings without motor: All parameters of the variable frequency drive, but
not the motor data parameters (P2xx), are reset to the factory setting.
Means that the function is switched off. No monitoring is performed. This is also the
[-02] = Auxiliary value 2
[-02] = Auxiliary value 2
S
P
[-03] = Auxiliary value 3
S
P
[-03] = Auxiliary value 3
BU 0200 en-US-3118