NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Value
Function
If the drive is to start up automatically when the mains is switched on (P428 = 1) a permanent high level must
be provided for enabling (supply control terminal 21 with 24 V).
If the "Enable right" and "Enable left" functions re actuated simultaneously, the VFD is blocked.
If the variable frequency drive is in fault status but the cause of the fault no longer exists, the error message is
acknowledged with a 1 → 0 flank.
03
Phase seq. reserval
04
1
Fixed frequency 1
05
1
Fixed frequency 2
06
1
Fixed frequency 3
07
1
Fixed frequency 4
If several fixed frequencies are actuated at the same time, they are added with the correct sign. In addition,
the analog setpoint (P400) and if necessary the minimum frequency (P104) are added.
08
5
Para Set Switching
"Parameter set changeover 1"
09
Hold frequency
10
2
Voltage disable
11
2
Quick stop
12
2
Fault acknowledgement
13
2
PTC resistor input
14
2, 4
Remote control
15
Jog frequency
1
16
Motor potentiometer
17
5
ParaSet Switching 2
"Parameter set changeover 2"
18
2
Watchdog
19
Setpoint 1 on/off
20
Setpoint 2 on/off
21
... 25 reserved for Posicon
176
Description
Causes the rotation field to change direction in combination with
Enable right or left.
The frequency from P465 [01] is added to the actual setpoint
value.
The frequency from P465 [02] is added to the actual setpoint
value.
The frequency from P465 [03] is added to the actual setpoint
value.
The frequency from P465 [04] is added to the actual setpoint
value.
Selection of active parameter set 1...4 - first bit.
During the acceleration or deceleration phase, a low level will
cause the actual output frequency to be "Held". A high level
allows the ramp to proceed.
The VFD output voltage is switched off; the motor coasts to a
stop.
The VFD reduces the frequency according to the programmed
fast stop time P426.
Fault acknowledgement with an external signal. If this function is
not programmed, a fault can also be acknowledged by a low
enable setting (P506).
Only with the use of a temperature monitor (bimetallic switching
contact). Switch-off delay = 2 s, warning after 1 s.
With bus system control, a low level switches the control to
control via the control terminals.
The frequency value from (P113) can also be set directly using
the HIGHER/LOWER buttons with a controller, Simple Box or
Parameter Box and stored in (P113) using the OK button.
If the device is operating with inching frequency, any bus
actuation that may be active is deactivated.
Same as setting 09 but the frequency is not maintained below the
minimum frequency P104 and above the maximum frequency
P105.
Selection of active parameter set 1...4 - second bit.
Input must see a high flank cyclically (P460), otherwise error
E012 will cause a shutdown. Function starts with the 1st high
flank.
SK 2x0E: Analog input switch-on and switch-off 1/2 (high = ON)
of the variable frequency drive
SK 2x5E: Analog input switch-on and switch-off 1/2 (high = ON)
of the first I/O extension. The low signal sets the analog input to
0% which does not lead to shutdown when the minimum
frequency (P104) > than the absolute minimum frequency (P505).
BU0210
Signal
High
High
High
High
High
High
Low
Low
Low
01
flank
High
High
High
Low
High
01
flank
High
High
BU 0200 en-US-3118