NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 591 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Parameter P728 – Netzs pannung @ 0\mod_1328173378202_14638.doc x @ 15132 @ @ 1
Input voltage
P728
(input voltage)
0 ... 1000 V
Displays the actual line voltage at the VFD input. This is determined indirectly from the value of
the DC link voltage.
Pos : 592 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Parameter P728 – Netzs pannung _ Statischer Betrag bei 24 V Geräten [SK 2xxE, SK 2xxE-FD S] @ 5\mod_1397203354385_14638.doc x @ 126308 @ @ 1
In devices with a separate 24 V supply, a static value is displayed if no line voltage is present
(e.g.: with 1~ 230 V devices: P728 = 230 V). This value is used for internal initialization
purposes.
Pos : 593 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Parameter P729 – Drehmoment @ 0\mod_1328173426559_14638.doc x @ 15133 @ @ 1
Torque
P729
(Torque )
-400 ... 400 %
Displays the actual calculated torque. Basis for calculation are the motor data P201...P209.
Pos : 594 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Parameter P730 – Fel d @ 0\mod_1328173473274_14638.doc x @ 15134 @ @ 1
Field
P730
(Field)
0 ... 100 %
Displays the actual field in the motor calculated by the VFD. Basis for calculation are the motor
data P201...P209.
Pos : 595 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Parameter P731 – Aktueller Parametersatz @ 0\mod_1328173520271_14638.doc x @ 15135 @ @ 1
Parameter set
P731
(current parameter set)
0 ... 3
Shows the actual operating parameter set.
Pos : 596 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Parameter P732 – Strom Phas e U @ 0\mod_1328173601208_14638.doc x @ 15136 @ @ 1
Phase U current
P732
(U phase current)
0.0 ... 999.9 A
Displays the actual U phase current.
NOTE:
This value can deviate somewhat from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
Pos : 597 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P700- P799/Parameter P733 – Strom Phas e V @ 0\mod_1328173830046_14638.doc x @ 15137 @ @ 1
Phase V current
P733
(V phase current)
0.0 ... 999.9 A
Displays the actual V phase current.
NOTE:
This value can deviate somewhat from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
Pos : 598 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265496 @ @ 1
214
Information
0 = Parameter set 1
1 = Parameter set 2
Display of static value
2 = Parameter set 3
3 = Parameter set 4