NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 652 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E005 [SK 180E/SK 2xxE/SK 5xxE/SK2xxE-FD S] @ 2\mod_1347453309234_14638.doc x @ 46527 @ @ 1
E005
5.0
Overvoltage DC link voltage
5.1
Power overvoltage
Pos : 653 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E006 [SK 5xxE, SK 2xxE, SK 2xxE-FD S] @ 2\mod_1361458416246_14638.doc x @ 58808 @ @ 1
E006
6.0
Charging error
6.1
Power undervoltage
Pos : 654 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E007 [SK 135E, SK 200E, SK 500E, SK xxxE-FD S] @ 2\mod_1361460459184_14638.doc x @ 58908 @ @ 1
E007
7.0
Power phase error
Pos : 655 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E008 [SK 2xxE] @ 2\mod_1347453314366_14638.doc x @ 46577 @ @ 1
E008
8.0
Parameter loss
(maximum EEPROM value
exceeded)
8.1
Inverter ID error, "Inverter
type incorrect"
8.2
Reserved
8.3
EEPROM KSE error
(Customer unit incorrectly
identified (customer's interface
equipment))
8.4
Internal EEPROM error
(Database version incorrect)
8.7
EEPROM copy differs, "EEPR
copy not the same"
Pos : 656 /Anleitungen/El ektr oni k/FU und Starter/6. M eldung en zum Betriebsz ustand/Stör meldung en (Auflistung)/F ehl er E009 "res er viert" [SK 180E/SK 2xxE/SK2xxE-FD S] @ 2\mod_1347453797027_14638.doc x @ 46702 @ @ 1
E009
---
Reserved
Pos : 657 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265496 @ @ 1
228
DC link voltage too high
•
Increase deceleration time (P103)
•
If necessary, set switch-off mode (P108) with delay
(not with lifting equipment)
•
Extend emergency stop time (P426)
•
Fluctuating speed (e.g. due to high centrifugal
masses), adjust U/f characteristic curve if
necessary (P211, P212)
Devices with brake chopper:
•
Reduce energy return using a braking resistor
•
Check the function of the connected braking resistor
(broken cable)
•
Resistance value of connected braking resistor too
high
Line voltage is too high
•
See technical data ( Section
DC link voltage is too low
•
Line voltage too low
•
See technical data ( Section
Line voltage too low
•
See technical data ( Section
Fault on supply connection side
•
a power phase is not connected
•
line power is asymmetric
Error in EEPROM data
•
Software version of the stored data set not
compatible with the software version of the VFD.
NOTE:
Faulty parameters are automatically reloaded
(default data).
•
EMC interferences (see also E020)
•
EEPROM faulty
The upgrade level of the variable frequency drive was not
correctly identified.
EEPROM with a firmware status of version 1.2 or above
plugged in to an VFD with older firmware status → Loss of
parameters! (also see Information in section 5)
•
Switch line voltage off and on again.
7
)
7
)
7
)