NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
Pos : 337 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P203 – Motor N enns trom @ 0\mod_1327588500455_14638.doc x @ 14915 @ @ 1
Motor Nominal current
P203
(rated motor current)
0.1 ... 1000.0 A
The rated motor current is a critical parameter for current vector control.
{ see information }
The default setting depends on the rated VFD output or the setting in P200.
Pos : 338 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P204 – Motor N enns pannung @ 0\mod_1327588687111_14638.doc x @ 14916 @ @ 1
Motor Nominal voltage
P204
(rated motor voltage)
100 ... 800 V
The >rated motor voltage< adjusts the line voltage to the motor voltage. In combination with the
rated frequency, the voltage/frequency characteristic curve is produced.
{ see information }
The default setting depends on the rated VFD output or the setting in P200.
Pos : 339 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P205 – Motor N ennl eistung @ 0\mod_1327588736705_14638.doc x @ 14917 @ @ 1
Motor Nominal power
P205
(Rated motor output)
0.00 ... 250.00 kW
The rated motor output controls the motor set via P200.
{ see information }
The default setting depends on the rated VFD output or the setting in P200.
Pos : 340 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P206 – Motor c os phi @ 0\mod_1327588784877_14638.doc x @ 14918 @ @ 1
Motor cos phi
P206
(motor cos
0.50 ... 0.95
The motor cos ϕ is a critical parameter for current vector control.
{ see information }
The default setting depends on the rated VFD output or the setting in P200.
Pos : 341 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P206 – Motor c os phi_Info_PM SM @ 19\mod_1505894620817_14638.doc x @ 2365515 @ @ 1
This parameter is not relevant if a PMSM is used.
Pos : 342 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P207 – Motorsc haltung @ 0\mod_1327589654065_14638.doc x @ 14919 @ @ 1
Star Delta con.
P207
(motor circuit )
0 ... 1
0 = star
{ see information }
The motor circuit is crucial for stator resistance measurement (P220) and therefore critical for
current vector control.
The default setting depends on the rated VFD output or the setting in P200.
Pos : 343 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265496 @ @ 1
148
Information
Information
Information
ϕ
)
Information
Information
1 = delta
Information
S
Default setting
S
Default setting
Default setting
S
Default setting
PMSM
S
Default setting
BU 0200 en-US-3118
P
P
P
P
P