Motor Nominal frequency
P201
(rated motor frequency)
10.0 ... 399.9 Hz
The rated motor frequency determines the V/f break point at which the VFD supplies the rated
voltage (P204) at the output.
{ see information }
The default setting depends on the rated VFD output or the setting in P200.
Pos : 335 /Anleitungen/El ektr oni k/FU und Starter/5. Par ameter/Par ameter auflistung (P000 ...)/P200- P299/Parameter P202 – Motor N enndrehz ahl @ 0\mod_1327588441470_14638.doc x @ 14914 @ @ 1
Motor Nominal speed
P202
(rated motor speed)
150 ... 24000 rpm
The rated motor speed is important for the correct calculation and control of motor slip and the
speed display (P001 = 1).
{ see information }
The default setting depends on the rated VFD output or the setting in P200.
Pos : 336 /Allgemein/Allgemeingültig e Module/---------Seitenumbr uc h kompakt --------- @ 13\mod_1476369695906_0.doc x @ 2265496 @ @ 1
BU 0200 en-US-3118
No change
No motor: In this setting the VFD operates without current control, slip compensation
and pre-magnetizing time, and is therefore not recommended for motor applications.
Possible applications are induction furnaces or other applications with coils and
transformers. In this case, the following motor data is set: