Nord Drivesystems NORDAC FLEX SK 200E Series User Manual page 243

Frequency inverters
Hide thumbs Also See for NORDAC FLEX SK 200E Series:
Table of Contents

Advertisement

Device model
Rated motor power
(4-pole standard motor)
Line voltage
Input current
Output voltage
FLA
Output current
3), 4)
Min. braking resistance
Motor mounting (ventilated), or wall mounting with SK TIE4-WMK-L-1 (or -2) (ventilated)
Max. continuous power/max. continuous current
Max. permissible ambient temp. with rated output current
S1
S3 70% ED 10 min
S6 70% ED 10 min (100%/20% Mn)
Wall mounting (unventilated)
Max. continuous power/max. continuous current
Max. permissible ambient temp. with nominal output current
S1
S3 70% ED 10 min
S6 70% ED 10 min (100%/20% Mn)
Class
CC, J, R, T, G, L
Bussmann FRS-
(≥ 230 V)
1) Pay attention to derating curve ( section 8.4.4 "Reduced output current due to line voltage").
2) FLA – Full-load current, maximum current for the entire line voltage range as stated above (200 V – 240 V) according to UL/CSA
3) FLA (S1-45°C), FLA motor mounting: relates to a motor with fans
4) SK 21xE and SK 23xE devices: For use of safe functions (functional safety: STO and SS1) the restrictions regarding the permissible temperature
range according to
BU 0230
must be noted.
5) Maximum permissible short-circuit current in the grid
6) The use of an SK TU4-MSW(-...) module limits the permissible short circuit in the grid to 10 kA
7) "inverse time trip type" in acc. with UL 489
a) 6.9 A when using a suitable fan
a) 8.8 A when using a suitable fan
a) 12.3 A when using a suitable fan
a) 15.7 A when using a suitable fan
BU 0200 en-US-3118
SK 2xxE...
-151-323-
Size
2
230 V
1.5 kW
240 V
2 hp
230 V
rms
1)
6.6 A
FLA
2)
6.6 A
230 V
rms
1)
7.0 A
2)
6.9 A
motor mounting
5.5 A
FLA
2)
wall mounting
(S1-40°C)
Accessories
62 Ω
S1-50°C
1.5kW/7.0A
S1-40°C
1.5kW/7.0A
50°C
50°C
50°C
4)
S1-50°C
0.55kW/3.8A
S1-40°C
0.75kW/4.8A
S1-30°C
1.10kW/5.7A
15°C
25°C
20°C
slow-blowing
16 A
Isc
5)
[A]
RK5
x
10 A
(x)
x
10 A
(x)
x
R-10
(x)
x
10 A
-221-323-
-301-323-
2
3
2.2 kW
3.0 kW
3 hp
4 hp
3 AC 200 ... 240 V, ± 10%, 47 ... 63 Hz
9.1 A
11.8 A
9.1 A
11.7 A
3 AC 0 ... line voltage
9.5 A
12.5 A
8.8 A
12.3 A
a)
5.5 A
b)
8.0 A
(S1-40°C)
(S1-40°C)
62 Ω
33 Ω
1.5kW/9.2A
3.0kW/12.5A
2.2kW/9.5A
3.0kW/12.5A
49°C
50°C
50°C
50°C
50°C
50°C
0.75kW/4.7A
1.1kW/6.8A
1.10kW/5.8A
1.5kW/8.7A
1.50kW/6.7A
2.2kW/10.4A
6°C
18°C
20°C
30°C
10°C
25°C
General fuses (AC) (recommended)
20 A
20 A
UL-approved fuses (AC)
30 A
30 A
30 A
30 A
R-30
R-30
25 A
25 A
7 Technical Data
-401-323-
3
4.0 kW
5 hp
15.1 A
14.9 A
16.0 A
15.7 A
c)
8.0 A
d)
(S1-40°C)
33 Ω
4)
3.0kW/14.5A
4.0kW/16.0A
46°C
47°C
47°C
1.1kW/6.8A
1.5kW/8.7A
2.2kW/10.4A
-4°C
0°C
0°C
25 A
30 A
30 A
R-30
25 A
243