TaiShan 200 Server
Maintenance and Service Guide (Model 2280)
Step 8 Take a spare PCIe card out of its ESD bag.
Step 9 Insert the PCIe card into a PCIe slot. See (1) in
Step 10 Close the latch. See (2) in
Figure 5-58 Installing a PCIe card on a riser module
Step 11 Install the riser module. For details, see
Step 12 Install the chassis cover. For details, see
Step 13 Install the server. For details, see
Step 14 Connect the power cables. For details, see
Step 15 Power on the server. For details, see
Step 16 Log in to the iBMC WebUI, and check whether the new component is normal. For
details, see the
----End

5.13 Battery

This section uses the server with Kunpeng 920 7260, 5250, or 5230 processors as
an example to describe the internal structure of a server. The procedures for
removing and installing the battery are the same for the server configured with
Kunpeng 920 5220 or 3210 processors.
Removing the Battery
Step 1 Wear an ESD wrist strap. For details, see
Step 2 Power off the server. For details, see