If the 10 kVA UPS is configured, do not connect the N cable.
If two 10 kVA UPSs are configured, connect the cables of the first UPS to the circuit breaker on
the left side and connect the cables of the second UPS to the circuit breaker on the right side.
If one 10 kVA UPS is configured, connect the cables only to the circuit breaker on the left side.
No switch is configured on the right side.
If one 20 kVA UPS is configured, connect the cables only to the circuit breaker on the left side.
No switch is configured on the right side.
If two 20 kVA UPSs are configured, connect the cables of the two UPSs to the circuit breaker
on the left side. No switch is configured on the right side.
4. (Optional) If two battery strings are configured,
connect cables from the UPS terminals + and – of
one battery string to the UPS terminals + and – of
the other battery string, as shown by (1) in the
figure. Connect cables to the UPS terminals, as
shown by (2) in the figure. Connect cables to the
battery terminals, as shown by (3) in the following
figure.
12.3

Installing a Battery Pack

1. Install mounting ears on a battery pack.
2. Install floating nuts at the installation position for the battery pack.
3. Install heavy-duty guide rails.
4. Secure the battery pack.
5. Install a protective cover for the battery rack.
27