FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Table 3-12 PDU2000 technical specifications
Item
Rated input voltage
Rated current
Input frequency
Input port
Output port configuration
Rated output current
3.2.2.6 Transformer
Table 3-13 Transformer technical specifications
Item
Rated capacity
Rated input current
Rated input voltage
input frequency
Output voltage
Output frequency
Efficiency (full load)
Dimensions (H x W x D)
Weight
3.2.3 (Optional) Battery Pack
Battery packs supply battery backup power. When the mains is normal, the UPS charges
batteries. When the mains fails, battery packs supply power to the UPS.
Issue 01 (2017-04-20)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Specifications (Vertically Installed
Full-Height PDU2000)
100–240 V
40 A
50 Hz/60 Hz
Cord end terminal, no input power cable
IEC: 20 x C13 + 2 x C19
40 A
Specifications
10 kVA
48 A
Dual-live wire 208 V
60 Hz
Single-phase 120 V
60 Hz
96%
430 mm x 650 mm x 130 mm
65 kg
3 System Architecture
32