Siemens SIRIUS M200D Manual page 180

Industrial controls, load feeders and motor starters, profibus / profinet
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Technical data
8.7 Switching frequency
Switching cycles/hour for 3RK1395-6LS71-.AD.(1.5 A to 12 A)
Installation position
Rated current I
e
Ambient temperature
Motor protection
Class 5 (10a)
ED=30 %, Start 4 x I
/ 1 s
e
ED=70 %, Start 4 x I
/ 1 s
e
ED=30 %, Start 4 x I
/ 2 s
e
ED=70 %, Start 4 x I
/ 2 s
e
Class 10
ED=30 %, Start 4 x I
/ 2 s
e
ED=70 %, Start 4 x I
/ 2 s
e
ED=30 %, Start 4 x I
/ 4 s
e
ED=70 %, Start 4 x I
/ 4 s
e
Class 15
ED=30 %, Start 4 x I
/ 3 s
e
ED=70 %, Start 4 x I
/ 3 s
e
ED=30 %, Start 4 x I
/ 6 s
e
ED=70 %, Start 4 x I
/ 6 s
e
Class 20
ED=30 %, Start 4 x I
/ 4 s
e
ED=70 %, Start 4 x I
/ 4 s
e
ED=30 %, Start 4 x I
/ 8 s
e
ED=70 %, Start 4 x I
/ 8 s
e
Duty cycle current rms value = 1.15 x I
1)
Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.
2)
180
Vertical
12 A
12 A
40 °C
50 °C
1)
2)
1)
2)
215
215
155
155
150
150
100
100
107
107
77
77
70
80
50
50
107
107
77
77
70
80
50
50
54
54
38
38
38
40
25
25
72
72
52
52
50
54
34
34
36
36
26
26
25
27
17
17
54
54
38
38
38
40
25
25
27
27
19
19
18
20
12
12
→ motor protection
e
Horizontal
12 A
12 A
55 °C
40 °C
1)
2)
1)
2)
125
125
175
175
70
70
125
125
63
63
88
88
35
35
62
62
63
63
88
88
35
35
62
62
312
31
44
44
18
18
31
31
42
42
59
59
24
24
41
41
21
21
29
29
12
12
20
20
31
31
44
44
18
18
31
31
15
15
22
22
9
9
15
15
Manual, 08/2014, A5E01577426A/RS-AA/004
12 A
11 A
50 °C
55 °C
1)
2)
1)
2)
125
125
120
120
70
70
70
70
63
63
60
60
36
36
33
33
63
63
60
60
36
36
33
33
31
31
31
31
18
18
18
18
42
42
40
40
24
24
24
24
21
21
20
20
12
12
12
12
31
31
31
31
18
18
18
18
15
15
15
15
9
9
9
9
M200D PROFIBUS/PROFINET