Response to overload temperature sensor
You use this parameter to specify how the motor starter is to respond in an overload
temperature sensor situation:
● Tripping without restart (AUTO RESET = off)
● Tripping with restart (AUTO RESET = on)
Motor restarts automatically if AUTO RESET is on.
Can Cause Death, Serious Injury, or Property Damage
The motor starter restarts automatically after the recovery time if a start command is
present (autoreset).
Make sure that you take appropriate measures to exclude the risk of hazardous conditions.
● Warning
Temperature sensor monitoring
Temperature sensor monitoring is activated when a PTC type A temperature sensor is
parameterized. It is then automatically deactivated if thermoclick is parameterized.
This device parameter monitors the temperature sensor cable for interruptions (wire break)
and short circuits. The motor is shut down (depending on the parameterization).
Settings
Response to overload temperature sensor
Temperature sensor
Temperature sensor monitoring
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
WARNING
Device parameter
Default setting
Tripping without
restart
Deactivated
Yes
Functions
3.6 Motor protection
Setting range
Tripping without restart
Tripping with restart
Warning
Deactivated
Themoclick
PTC type A
Yes
No
47