A.1.6

DS72 logbook - Read device error

Byte
Data type
0 ... 3
Unsigned 32
4 ... 5
Unsigned 16
6 ... 9
Unsigned 32
10 ... 11
Unsigned 16
...
...
120 ... 123
Unsigned 32
124 ... 125
Unsigned 16
The data record call "Logbook" returns the operating hour of the event that has occurred and
an associated object number for each entry. This data set can accommodate 21 entries.
When all locations have been overwritten, the oldest entry is overwritten again.
Note
The latest entry is entered at the first location of the data set. The remaining entries are
moved one entry down.
The supported object numbers and their meaning are shown in the table below:
Table A- 3
Object No.
451
452
453
454
456
457
458
460
461
462
308
1414
483
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
Meaning
Entry 1 (= latest entry)
Operating hours device
Object number
Entry 2
Operating hours - device
Object number
Entry 21
Operating hours - device
Object number
Assignment of object number to device error message
Device error - Messages
Temperature sensor not ready for operation
Heat sink thermistor defective
Faulty interface to current detection
Faulty SSC interface
EEPROM: memory defective
EEPROM: CRC error "Fixed-value parameter"
EEPROM: CRC error "Device parameter"
EEPROM: contains invalid data!
EEPROM: Invalid value for "Parameters disabled CPU/master"
EEPROM: Invalid pointer for device parameter buffer
Switching element defective
Switching element short-circuited
HMI module defective
A.1 Data formats and data sets
Range of values
0 ... 4 294 967 295
0 ... 32767
0 ... 4 294 967 295
0 ... 32767
0 ... 4 294 967 295
0 ... 32767
Appendix
Increment
1 s
1
1 s
1
1 s
1
197