Siemens SIRIUS M200D Manual page 116

Industrial controls, load feeders and motor starters, profibus / profinet
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Mounting / connection
4.2 Connection
Requirements
● The communication module is mounted on the motor starter module as shown in Chapter
Installing the communication module (Page 99).
● You have assigned the device name according to your configuration. Further information:
Assigning IO device names (PROFINET IO) (Page 123)
Required tools
● Screwdriver (PZ 2; 2 Nm)
● Stripping tool for wiring the M12 and 7/8" cable connectors, if you are fabricating your
own cables.
Required accessories
● Prefabricated cable with M12 and 7/8" cable connectors. The cables are available in
different lengths.
● If you are fabricating your own cable:
– M12: 4-core, shielded bus cable, and decoded M12 cable connector (PROFINET)
– 7/8": 4-core cable with 7/8" cable connectors
Pin assignment of the M12 and 7/8" cable connectors
PROFINET connection (M12)
Each port is connected via an M12 socket (D coding).
M12-D
116
Pin
Assignment
1
Transmission data + (TD+)
2
Receive data + (RD+)
3
Transmission data – (TD–)
4
Receive data – (RD–)
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents