Ds73 Logbook - Read Triggering Operations - Siemens SIRIUS M200D Manual

Industrial controls, load feeders and motor starters, profibus / profinet
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Appendix
A.1 Data formats and data sets
A.1.7

DS73 logbook - Read triggering operations

Byte
Data type
0 ... 3
Unsigned 32
4 ... 5
Unsigned 16
6 ... 9
Unsigned 32
10 ... 11
Unsigned 16
...
...
120 ... 123
Unsigned 32
124 ... 125
Unsigned 16
The data record call "Logbook" returns the operating hour of the event that has occurred and
an associated object number for each entry. This data set can accommodate 21 entries.
When all locations have been overwritten, the oldest entry is overwritten again.
Note
The latest entry is entered at the first location of the data set. The remaining entries are
moved one entry up.
The supported object numbers and their meaning are shown in the table below:
Object No.
309
317
318
319
324
325
326
327
333
334
335
338
341
348
354
1496
1497
198
Meaning
Entry 1 (= latest entry)
Operating hours - device
Object number
Operating hours - device
Object number
Operating hours - device
Object number
Trips - Messages
Switching element overload
Electronics supply voltage too low
No switching element supply voltage
No supply voltage
Temperature sensor - overload
Temperature sensor wire break
Temperature sensor - short circuit
Thermal motor model overload
Circuit breaker tripped
I
upper limit violation
e
I
lower limit violation
e
Residual current tripping
Asymmetry tripping
Input tripping
Sensor supply overload
Output 1 overloaded
Output 2 overloaded
Range of values
0 ... 4 294 967 295
0 ... 32767
Entry 2
0 ... 4 294 967 295
0 ... 32767
Entry 21
0 ... 4 294 967 295
0 ... 32767
Increment
1 s
1
1 s
1
1 s
1
M200D PROFIBUS/PROFINET