Advertisement

Settings
Response to overload - thermal
motor model
Trip class
Recovery time
Prewarning limit motor heating
Prewarning limit - remaining
time for tripping
Idle time
In the case of soft starters with startup mode = direct not parameterizable
1)
Messages and actions
Thermal motor model deactivated
Thermal motor model - overload
Overload tripping
Idle time active
Cooling time active
Prewarning limit - remaining time for
tripping undershot
Prewarning limit - motor heating
exceeded
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
Device parameter
Message
Default setting
Tripping without restart
CLASS 10
90 s
0% (= deactivated)
0 s (= deactivated)
0 s (= deactivated)
No motor protection via thermal motor model; motor
protection required by means of temperature sensor.
Dependent on parameterization
Trip (overload pending)
The motor is reset on expiry of the idle time
Restart is prevented until the cooling time has expired
(recovery time).
-
-
3.6 Motor protection
Setting range
Tripping without restart
Tripping with restart
Warning
CLASS 5 (10a)
CLASS 10
CLASS 15
1)
CLASS 20
1)
CLASS OFF
60 to 1800 s
Increment: 30 s
0 ... 95 %
Increment: 5 %
0 to 500 s
Increment: 1 s
0 to 255 s
Increment: 1 s
Action
Functions
45