A.1.16

DS131 Read/write device parameters

Complete data sets can be exchanged with the starters during operation via the acyclic
channel (PROFIBUS) and the NRT channel (PROFINET).
We recommend initially reading out data set 131 from the motor starter with the current
parameters, changing the corresponding parameters and then rewriting these to the motor
starter.
Please be aware that the coordination (Byte 0) is to be set to 0x21 prior to writing the data
set.
The following elements of data set 131 (138 bytes) are used to parameterize the M200D
PROFIBUS/PROFINET motor starters.
Object
Byte.Bit
Parameters / content
No.
0
Coordination
1
Reserved
2
Reserved
3
Reserved
120
4 ... 7
Device functions_2
1
8 ... 11
Device functions_1
130
14.0 ... 7
Rated operating current
and
I
A
e
15.0 to 7
3
16.0
Load type
4
16.1
Protection against
voltage failure
136
17.0 ... 7
Prewarning limit – motor
heating
5
18.0 ... 1
Response to overload
Thermal motor model
6
19.0 ... 3
Trip class
(2 A, 12 A)
7
20.0 ... 7
Recovery time
8
21.0 ... 7
Idle time
137
22 ... 23
Prewarning limit –
remaining time for
tripping
10
24.0 ... 1
Response to overload
temperature sensor
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
Range of values
Preamble
0x21 Write via acyclic bus channel (PLC)
0x00
0x00
0x00
Device parameter
MLFB-specific content,
see table 'Device functions' in connection with data set 131
0.15 ... 2.0 A
1.5 ... 12 A
[0] 3-phase motor
[1] 1-phase motor
[0] No
[1] Yes
0 ... 95 %;
[0] = deactivated
[0] Tripping without restart
[1] Tripping with restart
[2] Warning
[0] CLASS 10
[1] CLASS 20
[3] CLASS 5 (10a)
[4] CLASS 15
[15] CLASS OFF
1 min ... 30 min
0 s to 255 s ; 0 = deactivated
0 s to 500 s;
0 = deactivated
[0] Tripping without restart
[1] Tripping with restart
[2] Warning
A.1 Data formats and data sets
Increment
Default
setting
10 mA
0.15 / 2.0
1.5 / 12.0
[0]
[1]
5 %
[0]
[0]
5 (10a),
[0]
10,
15,
20,
CLASS OFF
0.5 min
1.5 min
1 s
0
1 s
0 s
[0]
Appendix
Relevant for
All starters
DSte / RSte
All starters
All starters
All starters
All starters
All starters
All starters
All starters
All starters
209