4.2.4

Installing and wiring power connectors

Hazardous voltage
Can Cause Death, Serious Injury, or Property Damage
Before starting work, disconnect the system and devices from the power supply.
Installa and wire the power connectors as follows:
Step
Procedure
1
Route the cable through the cable gland, sealing insert (enclosed), and the connector housing. The sealing
insert is available in the following gradings:
Permissible external diameter of the cable
7.0 to 10.5 mm
9.0 to 13.0 mm
11.5 to 15.5 mm
2
Strip the cable over a length of 20 mm.
3
Strip the cores over a length of 8 mm.
4
Secure the contact sockets/pins on the cores by crimping or soldering them.
5
Sort the contact sockets/pins in the socket/pin insert in accordance with the assignments (see section Power
terminal (Page 106)). The contact sockets/pins should not engage yet. Make sure that they are correctly
assigned. Push the contact sockets/pins into the socket/pin insert until they engage. Use a suitable tool to
remove contact sockets/pins that have already been installed (Han Q4/2: 3RK1902-0AB00, Han Q8/0:
3RK1902-0AJ00).
6
Make sure that the position of the coding is correct, pull the cable back, and secure the socket/pin insert in the
connector housing using the cross-recessed screws enclosed.
7
Secure the cable gland. When doing so, make sure that the cable is not twisted against the connector housing.
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
DANGER
Mounting / connection
Sealing insert
Green
Red
White
4.2 Connection