7.2

System diagnostics

System diagnostics
In the M200D PROFIBUS/PROFINET, device-specific diagnostics are recorded via assigned
PROFIBUS/PROFINET error codes.
System diagnostics indicate the existence of a channel fault. The existence of further
channel-related information is also indicated.
The stored values are extracted by the starter from the diagnostics captured in data set 92.
Since there are not sufficient uniquely defined DP/PN error codes available for the starter,
different DS 92 diagnoses must be mapped to one and the same error code (= multiple
assignment; see table).
Channel-specific diagnostics:
Single error
Short-circuit
Overload
Overtemperature
Wire break
Upper limit exceeded
Lower limit exceeded
Error
Parameter assignment error
No encoder or load voltage
Actuator disconnection
External error
In addition to the error code, error code 24 is set.
1)
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
DP/PN
DS 92
Error code
Byte.Bit
1
2.2
3.2
4
2.0
2.3
5
0.3
6
2.1
7
4.2
8
4.3
9
0.4
9.2
19.2
16
8.1
8.2
17
1.0
1.1
6.7
29.1
24
2.4
4.1
4.4
4.6
4.7
14.1
26
5.4
5.5
5.7
7.7
6.2
6.3
18.4-5
Meaning of the error
Temperature sensor short-circuit
Circuit breaker tripped
Temperature sensor overload
Thermal motor model overload
Switching element overload
Temperature sensor wire break
I
upper limit violation
e
I
lower limit violation
e
Switching element defective
Self-test error
Switching element short-circuited
Invalid parameter value (at startup only)
Parameters cannot be changed in ON state
No switching element supply voltage
No supply voltage
Electronics supply voltage too low
Mains connector removed on line side
Overload tripping
Asymmetry tripping
I
limit value tripping
e
Residual current tripping
Circuit breaker tripped
Tripping due to motor blocking
Cold run tripping
Input tripping
Input trip end position CW
Input trip end position CCW
Process image error
Quick stop active
Sensor supply overload
Output overloaded
Diagnostics
7.2 System diagnostics