Configuration / parameterization

5.2 Parameterize

5.2
Parameterize
5.2.1
Parameter dependencies in the GSD/GSDML
Note
When parameterizing with the GSD/GSDML file, values can be selected that are mutually
dependent and are not permissible in combination! The relevant parameter is reported as
"Invalid parameter value" in data set 92!
The following table shows which parameters are mutually dependent and how they must be
set:
Dependent parameters
Current limit values
Temperature sensor deactivated
CLASS OFF
Startup mode
Max. rated operating current I
Startup mode
Trip class CLASS
Maintenance timer warning limits Maintenance timer warning limit 1 < maintenance timer warning
Input n signal
Input n level
Input n action
126
Setting
Lower current limit < upper current limit
With CLASS OFF: "Temperature sensor deactivated" not possible
with "Temperature sensor deactivated": "CLASS OFF" not
possible
(only for sDSSte, sRSSte with I
with direct startup mode: I
e
(only for sDSSte, sRSSte)
with direct startup mode: Restriction to CLASS 5 (10a), 10 and
CLASS OFF
limit 2
Dependencies, see Chapter Inputs (Page 53)
= 12 A)
e, max
= 9.0 A
e,max
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004