Siemens SIRIUS M200D Manual page 171

Industrial controls, load feeders and motor starters, profibus / profinet
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Motor starter version
Motor ratings according to UL / CSA
3RK13.5- .K (2 A)
power (3ph /hp) / max. FLA
3RK13.5- .L (12 A)
power (3ph /hp) / max. FLA
Typical switching times incl. internal
signal processing
at 0.85 to 1.1 x U
e
Mechanical service life of contactor
Electrical service life of contactor
B10 value
Permissible switching frequency
Isolation stability
Rated surge capacity U
imp
Rated insulation voltage U
Safe isolation between main and control circuits
to IEC 60947-1 Appendix N
Short-circuit protection
Instantaneous overcurrent release
I
= 2 A
e max
I
= 9 / 12 A
e max
Rated short-circuit¬breaking capacity I
IEC 60947
At 400 V
At 500 V
Short circuit ratings according to UL / CSA
Group installation
Motor disconnect
1) This specification refers exclusively to the mechanical switching element under its reference conditions.
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
At 460/480 V AC
At 575/600 V AC
At 230/240 V AC
At 460/480 V AC
At 575/600 V AC
Closing delay
Opening delay
i
at 400 V in accordance with
CU
PROFIBUS/PROFINET
DSte / RSte
0.75 hp / 1.6 A
1 hp / 1.7 A
3 hp / 9.6 A
7.5 hp / 11 A
10 hp / 11 A
50 to 85 ms
40 to 65 ms
10 million
Electrical service life of
contactor (Page 183)
1000000
1)
Electrical service life of
contactor (Page 183)
6 kV
500 V
400 V
26 A
208 A
50 kA
50 kA
65 kA / 480 V /
Any circuit breaker or
any fuse
10 kA / 600 V /
Any circuit breaker or
any fuse
Suitable for Group installation
Suitable as motor disconnect
Technical data
8.2 Motor starters
sDSSte/sRSSte
0.75 hp / 1.6 A
3 hp / 9.6 A
7.5 hp / 11
25 / 105 ms
35 / 35 ms
Switching frequency
(Page 175)
50 kA
20 kA
5 kA / 480 V /
fuse: 60 A class J
42 kA / 480 V /
fuse: 45 A class J
171

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents