Siemens SIRIUS M200D Manual page 76

Industrial controls, load feeders and motor starters, profibus / profinet
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Functions
3.15 Factory settings
Test steps
The self-test comprises 3 test steps. The test steps are followed in dependence of the signal
duration of the test command:
Test step
This test step is only executed in manual mode
1)
Self-test error
If an error occurs, the "DEVICE" LED lights up red. The error can only be acknowledged by
switching the device off and then on again. If the error is still present, the self-test will return
an error again when the device is switched on. In this case, the motor starter must be
replaced.
Messages and actions
Self-test active
Self-test ok
Self-test error
Note
Specific device components are monitored continuously (internally) by the motor starter and
the results signaled with the self-test messages. The message "Self-test error" can also
appear in the case of an internal monitoring fault without the self-test having been activated.
76
Signal
duration
1
< 2 s
2
2 to 5 s
3
> 5 s
1)
Messages
Test scope
LED test
All LEDs are switched on for 2 seconds!
User check, no message bit
Hardware test The hardware of the motor starter is tested;
Current measurement indicated by the "DEVICE" LED:
Current flowing: flashing red
Current not flowing: flickering red
User check, no message bit
Trip
Switching elements are switched off.
Explanations
Actions
-
-
-
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004