Firmware update of the PROFINET communication module

Introduction
After you have implemented (compatible) functional expansions or enhanced performance at
the PROFINET communication module, you must update it with the latest firmware version.
You can obtain the most recent firmware versions from your Siemens representative, or
download them from the Internet. (http://www.siemens.com/automation/service&support)
Note
If the new firmware cause any problems, you can restore the previous firmware to the
communication module. You can also download this from the Internet.
Requirements
● Prior to the update note down the current version of your firmware. You can read the
version number in HW Config.
● Online FW updates can be performed in STEP 7 V5.4 + SP5 or higher.
● The communication module whose firmware is to be updated must be accessible online.
● The files ("*.UPD") containing the current firmware version must be available in the file
system on your PG/PC. A folder may contain only the files of one firmware version.