Factory Settings - Siemens SIRIUS M200D Manual

Industrial controls, load feeders and motor starters, profibus / profinet
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

3.15

Factory settings

Description
The factory setting restores the settings of the motor starter as supplied, that is, the motor
model is deleted, faults are reset (if possible), and the operating hours counter is deleted,
etc.
This provides the option of resetting the motor in the event of incorrect parameterization.
Note
Current maximum pointer and statistical data are not deleted.
Restoring factory settings
● With the "Factory settings" command (via data set 93 or Motor Starter ES).
This is only possible if the "Manual" mode is set and the switching elements are switched
off.
● With the disconnecting means
Turn the knob of the disconnecting means within the specified time window of 2 to 4
seconds to the positions ON and OFF as shown in the time diagram below, and monitor
the LEDs on the motor starter as you do so.
Figure 3-10
Factory settings
The introduction sequence prevents accidental resetting to the factory setting values.
The factory setting operation is introduced with the beginning of the start sequence. The
LEDs behave as follows here:
● SF off
● STAT off
● DEVICE flashes red
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
Functions
3.15 Factory settings
77