Periphery Board (2-Loop); Installation - Siemens FS720 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

Installing, exchanging and connecting modules
6

Periphery board (2-loop)

6.2 Periphery board (2-loop)

6.2.1 Installation

48 | 222
Building Technologies
Fire Safety
The periphery board (2-loop) FCI2002-A1 is mounted in the fire control panels in
the factory and only has to be replaced in the event of a repair.
1
X1
Figure 24: Mounting of periphery board (2-loop)
1
Threaded bolts on rear panel
2
9 fixing screws
3
Periphery board (2-loop)
X1
Connector for supply
X3
Connector for connection cable to PMI & mainboard (operating unit)
X400 Connector for periphery bus
ϖ Components that make access to the periphery board difficult are removed
(e.g. mounting plate).
ϖ Connections and plug-in contacts are disconnected and the cables are
labelled.
ϖ The periphery board is removed.
1. Mount the periphery board (3) with the nine fixing screws (2) to the threaded
bolts (1) in the rear panel.
2. Wire up the periphery board (2-loop) according to the pin assignment.
3. Re-install any modules that you may have had to remove.
X6 X12 X11
X7
X8
X9
X3
X400
2
3
A6V10210390_j_en_--
2015-12-15

Advertisement

Table of Contents
loading

Table of Contents