A.2.5: Using Type Codes For Releasing Zones - Honeywell Notifier NFS2-640/E Programming Manual

Fire alarm control panel
Hide thumbs Also See for Notifier NFS2-640/E:
Table of Contents

Advertisement

How to Program a Releasing Zone
A.2.5 Using Type Codes for Releasing Zones
The control panel provides a set of Type Codes designed for releasing applications for inputs and
outputs. This section details how to program each of these Type Codes.
Type Codes designed for Releasing Zone inputs (monitor modules).
Type Code
ABORT SWITCH
(tracking)
.
MAN
RELEASE
(latching)
MAN REL DELAY
(latching)
SECOND SHOT
(latching)
Type Codes designed for Releasing Zone outputs (control modules and panel NACs).
Type Code
REL END BELL
REL CKT ULC
RELEASE CKT
RELEA
REL AUDIBLE
INSTANT RELE
REL CODE BELL
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
What the Type Code does
Provides an abort function through a monitor
module (connected to a UL-listed abort
station) for a Releasing Zone.
Provides a manual release through a monitor
module (connected to a UL-listed pull station)
for a Releasing Zone.
Provides a manual release with a 30-second
delay (dependent on the FACP Delay setting)
through a monitor module (connected to a
UL-listed pull station) for a Releasing Zone.
Provides a second manual release through a
monitor module (connected to a UL-listed
pull station) for a Releasing Zone.
What the Type Code does
Activates a NAC audio or visual device
when releasing circuits shut off.
Directs outputs to perform a release function
as required by ULC.
Directs outputs to perform a releasing
function.
.
Directs relay outputs to perform a releasing
FORM C
function.
Activates audio or visual devices steady
when releasing starts.
Activates non-releasing output (panel NAC
or control modules) with no delay time.
Activates audio or visual devices to pulse at
20 ppm (initial zone of a Cross Zone) or 120
ppm (Cross Zone satisfied).Steady on
release.
Releasing Applications
Refer to
"abort switch Type Code" on page 74
"man. release Type Code" on page
75
"manrel delay Type Code" on page
76
"second shot Type Code" on page 78
Refer to
"release end bell" on page 79
"rel ckt ulc Type Code" on page 81
"release ckt Type Code" on page 83
"Relea. Form-C Type Code" on page
85
"rel audible Type Code" on page 87
"instant rele Type Code" on page 89
"REL CODE BELL Type Code" on
page 90
73