Honeywell Notifier NFS2-640/E Programming Manual page 32

Fire alarm control panel
Hide thumbs Also See for Notifier NFS2-640/E:
Table of Contents

Advertisement

Programming
System Function
USA TIME
TERM - Allows supervision for devices connected
to TB11, i.e., FDU-80.
AC_DLY**
LocX - One of three operating modes of PC or
terminal connected to the control panel through
TB12 on the CPU2-640.
Note: For a complete list of functions, refer to the
NFS2-640 Operations Manual.
BLINK - Addressable SLC device LED blink.
ST - The NFPA wiring style used for the SLC.
ACS - Use ACS Selection Groups (Refer to
"Annunciator Options" on page 33).
*This value can not exceed 30 seconds for ULC installations.
**The onboard trouble relay will activate (TB4 on the NFS2-640 CPU) and TM-4s will report according to this setting. UDACTs
and UDACT-2s are notified immediately of AC failure by the panel, regardless of the panel's delay setting. Once the UDACT
or UDACT-2 receives notification, it operates according to its own programmed AC Fail Delay reporting schedule.
Example: AC Failure occurs at 1:00 p.m. on a panel with an AC_DLY setting of Y (3 hours). The UDACT/UDACT-2 is set for
notification after 1 hour.
1:00 p.m. - AC Failure. Panel notifies UDACT/UDACT-2. Panel and UDACT/UDACT-2 timers begin countdown to report
time.
2:00 p.m. - UDACT/UDACT-2 reports.
4:00 p.m. - TM-4 reports, TB4 trouble relay activates.
The ACPS-610 and ACPS-2406 power supplies must be set to an AC Delay value of 0 (zero) when used with this panel.
32
Table 2.12 Settings for Global Systems Functions (2 of 2)
Setting
USA time (mm/dd/yy) or
EUR time (dd/mm/yy)
Press the
(European) time changes to 24-hour time format and date
format.
N = no supervision
Y = supervision enabled
AC delay – delays loss of AC reporting for 3 hours.
Y=AC delay; N=no AC delay
LocT -(terminal connected to control panel and located in
same room).
LocM -(same as LocT but requires password).
RemT -(terminal connected through a modem for Read Status
only).
Select from 00 to 16.
(00 = no blink, 01 = blink every poll, 02 = blink every 2nd poll,
03 = blink every 3rd poll up to 16 = blink every 16th poll).
Note that this setting affects FlashScan modules only.
6=Style 6 SLC wiring
4=Style 4 SLC wiring
N or Y
or
key to change. Note that
NEXT
PREVIOUS
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Basic Program
Default
USA
N
Y
LocT
01
4
N