Honeywell Notifier NFS2-640/E Programming Manual page 113

Fire alarm control panel
Hide thumbs Also See for Notifier NFS2-640/E:
Table of Contents

Advertisement

Type Codes for Input Devices
SUP.L(DUCTP)
2,3
SUP.T(PHOTO)
2
SUP.L(PHOTO)
RF_PHOTO
1
SMOKE(HARSH)
4
PHOTO/CO
PHOTO/CO (P
2,4,5
SUP)
4
PHOTO/CO (C SUP)
SMOKE(BEAM)
SMOKE(LASER)
2
SUP.L(LASER)
2,3
SUP.T(LASER)
SMOKE(DUCTL)
SUP T(DUCTL)
SUP L(DUCTL)
AIR REF
NOTE: A reference detector still functions as a smoke detector, but you should set the detector sensitivity level to the least sensitive level—AL:9 and
PA:9 Change Alarm and Pre-Alarm sensitivity. Refer to "Detector Sensitivity Settings" on page 101 for a complete list of detector sensitivity settings.
HEAT
HEAT+
HEAT(FIXED)
HEAT (ROR)
SMOKE ACCLIM
SMOKE(ACCLI+)
1
SMOKE(MULTI)
ASPIRATION
ASPIR (SUP)
ASPIR (PRE)
ASPIR (NON)
ASPIR (REF)
NOTE: Aspiration detector (FAAST) programming requires 5 SLC addresses.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Table F.1 Intelligent Detector Type Codes (2 of 3)
supervisory
Y
lights supervisory LED
supervisory
N
lights supervisory LED
supervisory
Y
lights supervisory LED
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED for photo and heat,
no LED will light for a CO alarm,
photo and heat will activate CBE, CO
alarm activates special function zone FC
and sixth CBE zone only (sixth CBE zone
programmable via VeriFire Tools)
fire alarm/
Y
lights fire alarm LED for heat, no LED will
supervisory
light for a CO alarm, supervisory LED will
light for photo alarm,
heat and photo will activate CBE, CO
alarm activates special function zone FC
and sixth CBE zone only (sixth CBE zone
programmable via VeriFire Tools)
fire alarm/
Y
lights fire alarm LED for heat and photo
supervisory
alarms, will light supervisory LED for CO
alarm, photo and heat alarms will activate
CBE, CO alarm will activate sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
supervisory
Y
lights supervisory LED
supervisory
N
lights supervisory LED
fire alarm
Y
lights fire alarm LED and activates CBE
supervisory
N
lights supervisory LED
supervisory
Y
lights supervisory LED
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
supervisory
Y
lights supervisory LED and activates CBE Aspiration detector supervision
prealarm
N
lights prealarm LED and activates CBE
non-fire
N
activates CBE
non-fire
N
activates CBE
Photoelectric smoke detector used as a duct detector
to report supervisory condition rather than alarm.
Latching.
Photoelectric smoke detector used to report
supervisory condition rather than alarm. Tracking.
Photoelectric smoke detector used to report
supervisory condition rather than alarm. Latching.
Wireless Photoelectric smoke detector
HARSH smoke detector
Photoelectric, Carbon Monoxide, and Heat detector
Photoelectric, Carbon Monoxide, and Heat detector
Photoelectric, Carbon Monoxide, and Heat detector
Beam smoke detector
Laser smoke detector
Laser smoke detector used to report supervisory
condition rather than alarm. Latching.
Laser smoke detector used to report supervisory
condition rather than alarm. Tracking.
Duct Laser smoke detector
Laser smoke detector used as a duct detector to
report supervisory condition rather than alarm.
Tracking.
Laser smoke detector used as a duct detector to
report supervisory condition rather than alarm.
Latching.
Assign to one or more FSL-751 detectors used to
monitor the quality of air entering the protected area.
The air quality measurement allows the VIEW
system to compensate for vehicle fumes, fog, or other
particles brought into the protected area through the
ventilation system. Poor air quality will lower the
sensitivity of all FSL-751 detectors on the SLC. The
detector sensitivity, however, remains within approved
limits (always less than 1% obscuration per foot).
o
190
F intelligent thermal sensor
o
190
F intelligent thermal sensor with low temperature
warning.
o
135
F intelligent thermal sensor
o
15
F per minute rate-of-rise detector
Combination Photoelectric/heat detector without
freeze warning (Acclimate Plus™)
Combination Photoelectric/heat detector with freeze
warning (Acclimate Plus™, or IntelliQuad FSC-851
Photoelectric Multi-Criteria Smoke Sensor)
Multisensor smoke detector
Aspiration smoke detector
Aspiration detector prealarm
Aspiration detector non-alarm
Used as a reference for other aspiration detectors on
the loop
Type Codes
®
113