Appendix H: Intelligent Sounder Base Programming
The NFS2-640 is compatible with the B200 Intelligent Sounder Base. This sounder base allows for
multiple tone generation that is user programmable via VeriFire Tools.
Programming the Intelligent Sounder Base into the Control Panel:
Once the sounder base has been installed and a detector has been plugged into the sounder base,
you can do one of the following to program the sounder base into the control panel:
Autoprogram—Perform an autoprogram at the control panel. The sounder base will have the
same SLC device address as the detector installed on the sounder base. Once the Autoprogram
is performed, the display will show the number of sounder bases installed on the control panel.
Refer to Section 2.3.2, "Autoprogram the Control Panel (1=auto)", on page 15.
VeriFire Tools —Using VeriFire™ Tools, program the detector that is to be installed in the
sounder base and select the Intelligent Sounder Base option. Refer to the VeriFire Tools Help
File for additional information.
Intelligent Sounder Base Options:
The sounder base has user programmable options that can be modified via VeriFire Tools. These
features and their defaults are as follows:
Feature:
Zone Mapping
Silence and
Resound
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
and Operation
Table H.1 Intelligent Sounder Base Options
Description and Options:
The sounder base allows for up to three (3)
zones to be programmed for specific tone
generation. The tones available are:
• Continuous
• Temp-3
• Temp-4
• March Time
The first of the three zones has the highest
priority, the second zone has second priority,
and the third has third priority.
The intelligent sounder base may be
programmed for silenceable operation as well
as signal resound. The silence and resound
options available are:
• No silence
• Silence and resound by Fire Alarm
• Silence and resound by Supervisory
• Silence and resound by CO alarm
• Silence and no resound
Default:
No zones mapped.
(When set as default, a fire alarm
will generate a Temp-3 tone and a
CO alarm will generate a Temp-4
tone.)
Silenceable and Resound by Fire