Honeywell Notifier NFS2-640/E Programming Manual page 29

Fire alarm control panel
Hide thumbs Also See for Notifier NFS2-640/E:
Table of Contents

Advertisement

Basic Program
Special Function
F2 (AC Trouble)
F3 (Security)
F4 (Supervisory)
Selecting Special Zones
Select Special Zones by entering the Special Zone letter and number (for example, F0, R0, and so
on) from the Special Function Change screen. The following sections show sample screens that
display when you select a Special Zone.
F0 (Presignal/PAS) The Presignal screen provides fields for changing the delay time or PAS. For
details on Presignal selections, refer to "Presignal and PAS Time" on page 92. From the Special
Function Change screen, press the F key, then press the 0 key to display the Presignal Function
screen.
Presignal delay time:
60-180 seconds
R0-R9 (Releasing Functions) The Releasing Function screen provides fields for changing
releasing functions: Delay Timer, Abort
releasing applications, refer to "NFPA Releasing Applications" on page 61.
NOTE: The FCM-1-REL has an inherent two second delay, which must be factored into the
DELAY TIME and SOK (soak time) entries.
From the Special Function Change screen, select a function (R0-R9) to display the Releasing
Function screen:
Delay Timer for
releasing application:
1-60 seconds or 00
(no delay)
Abort Switch: a thee-letter Abort switch
Type Code (ULI, IRI, NYC, or AHJ)
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Table 2.11 Special Output Functions F1-F4 (2 of 2)
Specifies
An output programmed to turn on/off if an AC power loss or a
brownout condition occurs
An output programmed to turn on/off if a Security input activates
An output programmed to turn on/off if a Supervisory input
activates
Presignal programming status banner
P R G P R E S I G N A L F U N C T
D E L A Y = 1 8 0
Switch
Releasing Zone programming status banner
P R G R E L E A S E F U N C T
D E L A Y = 0 0 A B O R T = U L I
P R E S I G N A L D E L A Y
P A S = N O
PAS selection: YES (PAS selected)
or NO (PAS not selected)
, Cross Zone, and Soak Timer. For details on
R E L E A S E C O N T R O L
C R O S S = N S O K = 0 0 0 0 R 0 0
Cross Zone option: specifies type of
Cross Zone: N (none), Y, Z, or H
Programming
F 0 0
Presignal
(zone F0)
Releasing zone
(R0 shown)
Soak Timer option:0000
(not used) or delay time
(0001-9999 seconds)
29