Releasing Applications
Programming a ULI Abort Switch
The following contains information needed to program a ULI Abort Switch.
Description
Requires a standard UL-type delay timer that complies with UL Standard 864.
How to Program
1.
2.
To Program
ULI Abort Switch
3.
How It Works
When an alarm initiates in the programmed Releasing Zone, you can press and hold the Abort
Switch while the Delay Timer continues to count down. (If the delay timer has expired, the abort
switch has no effect.) When you release the Abort Switch, a 10-second ULI timer counts down. At
the end of the 10-second ULI timer, the control panel activates the Releasing Zone outputs.
Example
A ULI Abort Switch and a Delay Timer programmed to Releasing Zone R05:
64
Program the monitor module connected to the abort station with the Type Code
as detailed in "Modify an Addressable Monitor Module Point" on page 22.
SWITCH
Select a time for the Releasing Zone Delay Timer (refer to"Programming a Delay Timer"
on page 61).
Do this
Type ULI in the ABORT= field, or press the
keys:
Press
at this point to save the Abort Switch value if no other fields on the screen
are changing. To change another field on the screen, move the cursor into position by
pressing the arrow keys on the keypad.
P R G R E L E A S E F U N C T
D E L A Y = 1 5
A B O R T = U L I C R O S S = N S O K = 0 0 0 0
Program selections for Releasing Zone R05
Delay =15 sec.
0 sec.
5 sec.
5 sec.
Alarm
Press and hold the
Abort Switch for 15
seconds
Figure A.4 ULI Abort Switch Example
How to Program a Releasing Zone
or
until ULI appears in the field.
R E L E A S E C O N T R O L
Total time from alarm initiation to release:
5 + 15 + 10 = 30 seconds
15 sec.
20 sec.
15 sec.
10 sec.
Release the Abort
Switch; the 10-second
ULI timer begins
When the 10-seconds
ULI timer expires, the
control panel activates
Releasing Zone outputs
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
ABORT
or
NEXT
PREVIOUS
R 0 5
30 sec.