F.1: What Are Type Codes; F.2: How To Select A Type Code; F.3: In This Appendix; F.4: Type Codes For Input Devices - Honeywell Notifier NFS2-640/E Programming Manual

Fire alarm control panel
Hide thumbs Also See for Notifier NFS2-640/E:
Table of Contents

Advertisement

F.1 What are Type Codes?
Type Codes are software selections for initiating devices (detectors and monitor modules) and
output devices (control modules and NACs). Some Type Codes are self-explanatory; that is, the
Type Code matches the function of the device, such as a "Monitor" for a monitor module, "Photo"
for a photoelectric detector, and so on. Type codes also provide special functions, such as activating
switches, solenoids, and control panel functions.
F.2 How to Select a Type Code
You select a Type Code through the Point Programming screen. For instructions, refer to "Modify
an Addressable Detector Point" on page 20.
F.3 In this Appendix
This appendix contains detailed descriptions of Type Codes for input and output devices, as listed
below:
F.4 Type Codes for Input Devices
F.4.1 Overview
This section provides Type Codes for intelligent detectors and monitor modules. For instructions on
programming Type Codes, refer to "Modify or Delete a Point (2=point)" on page 19.
F.4.2 Type Codes for Intelligent Detectors
A list of intelligent detector Type Codes, which specify the type of detector installed at an SLC
address.
Type Code
SMOKE (ION)
SMOKE(DUCTI)
3
SUP.T(DUCTI)
SUP.L(DUCTI)
2,3
SUP.T(ION)
2
SUP.L(ION)
SMOKE(PHOTO)
SMOKE(DUCTP)
3
SUP.T(DUCTP)
112
Appendix F: Type Codes
Type of Device
F.4.2, "Type Codes for Intelligent Detectors"
F.4.3, "Type Codes for Monitor Modules"
F.5.2, "Type Codes for Control Modules"
F.5.3, "NAC Type Codes"
Table F.1 Intelligent Detector Type Codes (1 of 3)
Point Characteristics
Latching
Point Type
Point Function
(Y/N)
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
supervisory
N
lights supervisory LED
supervisory
Y
lights supervisory LED
supervisory
N
lights supervisory LED
supervisory
Y
lights supervisory LED
fire alarm
Y
lights fire alarm LED and activates CBE
fire alarm
Y
lights fire alarm LED and activates CBE
supervisory
N
lights supervisory LED
Refer to page
page 112
page 114
page 115
page 116
Device Function
Ionization smoke detector
Duct Ionization smoke detector
Ionization smoke detector used as a duct detector to
report supervisory condition rather than alarm.
Tracking.
Ionization smoke detector used as a duct detector to
report supervisory condition rather than alarm.
Latching.
Ionization smoke detector used to report supervisory
condition rather than alarm. Tracking.
Ionization smoke detector used to report supervisory
condition rather than alarm. Latching.
Photoelectric smoke detector
Duct Photoelectric smoke detector
Photoelectric smoke detector used as a duct detector
to report supervisory condition rather than alarm.
Tracking.