Honeywell Notifier NFS2-640/E Programming Manual page 105

Fire alarm control panel
Hide thumbs Also See for Notifier NFS2-640/E:
Table of Contents

Advertisement

Detector Maintenance Features
6.
Alarm Reading (000%) The current alarm reading of the detector, as a percentage of the
Alarm Sensitivity setting.
7.
Alarm Sensitivity Setting (A8) The Alarm Sensitivity (x=1-9) entered in the Detector
Sensitivity Screen.
8.
Pre-Alarm Sensitivity Setting (8) The Pre-Alarm Sensitivity (1-9; 0 = Pre-Alarm not used)
entered in the Detector Settings Screen. Refer to "Detector Sensitivity Settings" on page 101
for more information on the Pre-Alarm sensitivity settings.
9.
Multi-Detector Selection (*) A smoke detector programmed so that it evaluates readings from
nearby detectors in making Alarm or Pre-Alarm decisions. Cooperative Multi-Detector
sensing also allows the combination of ionization with photoelectric technology in reaching an
alarm decision. See "Modify an Addressable Detector Point" on page 20 for instructions on
setting Cooperative Multi-Detector Settings.
* – Multi-not used.
A – combines the detector's alarm decision with the next address above.
B – combines the detector's alarm decision with the next address below.
C – combines the detector's alarm decision with the next address above and the next address
below.
10. Alarm Verification (*)
* – Alarm Verification not programmed for this detector.
V– Alarm Verification enabled.
xx – Alarm Verification programmed for the detector; xx equals the Verification Counter (00-
99). See "Modify an Addressable Detector Point" on page 20 for instructions on setting Alarm
Verification.
11. Device SLC Address (1D044) The SLC address of the detector.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Intelligent Sensing Applications
105