How to Program a Releasing Zone
Example 1: If the detector initiates the alarm, R05 activates. Releasing begins after the delay timer
has expired (15 seconds). Releasing will continue for the soak timer duration (30 seconds). Once
the Soak Timer expires, the Second Shot Switch can then be activated to initiate an additional soak
cycle.
Example 2: If the NBG-12LRA (Type Code
begins its 15 second countdown. Releasing will begin after the delay timer has expired, and will
continue for the soak timer duration (30 seconds). Once the Soak Timer expires, the Second Shot
Switch can then be activated to initiate an additional soak cycle.
RELEASE END BELL
NOTE: A releasing circuit with this Type Code requires the following selections: A Releasing
Zone selection (R0-R9); An output circuit mapped to the same Releasing Zone; Switch Inhibit
selected; Non-Silenceable; No Walk Test.
The following contains information needed to program a Release End Bell circuit for a control
module or a NAC
Description
A control module or NAC to activate an audible or visual device when releasing devices shut off.
You can also program multiple outputs with the
Zone. When all the Releasing Zone functions are complete, all outputs with the
Code activate at the same time. A
Programming
1.
Select a control module or NAC (refer to "Modify or Delete a Point (2=point)" on page 19) to
use as a Release End Bell circuit.
2.
Select the
shown).
3.
Select the Releasing Zone (R0-R9) for your releasing application.
4.
Press the enter key to save, then press the esc key two times to return to the Program Change
screen.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
.
REL END BELL
Type Code, as shown in the following example (control module
REL END BELL
P R O G R M R E L E N D B E L L M O D U L E A D D R 2 M 1 0 8
Releasing Zone
selection (R5 shown)
Switch Inhibit: I = selected
) lever is pulled, the delay timer
MANREL DELAY
Type Code to the same Releasing
REL END BELL
circuit remains on until you reset the system
Type Code selection:
REL END BELL
R 5 _ _ _ _ _ _ _ _
Releasing Applications
Type
REL END BELL
I * *
2 M 1 0 8
Walk Test
Selection: * = off
Silenceable: * = off
79