How to Program a Releasing Zone
.
MAN
RELEASE
The following contains information needed to program a Manual Release switch for a monitor
.
module
Description
A monitor module—connected to a UL-listed manual station (such as the Notifier NBG-12LRA)—
used to manually release agents. A Manual Release switch overrides all timers, such as a Delay
Timer or a Soak Timer. You can install multiple monitor modules with a
that work like multiple conventional manual release switches on a conventional zone.
Programming
1.
Select a monitor module (refer to "Modify or Delete a Point (2=point)" on page 19) to use for
the manual release function.
2.
Select the
3.
Select the Releasing Zone (R0-R9) for your releasing application.
4.
Press the
screen.
Example
A programming example of a monitor module programmed as an manual release switch for
Releasing Zone R5.
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Type Code
.
Type Code.
MAN
RELEASE
P R O G R M M A N _ R E L E A S E
key to save, then press the
ENTER
SYSTEM
SYSTEM
NORMAL
ACTIVATED
NBG-12LRA station with Manual Release Lever
Type Code
.
MAN
RELEASE
Figure A.11 Monitor Module Configured as a Manual Release Switch
Type Code selection:
M O D U L E A D D R 2 M 1 0 1
R 5 _ _ _ _ _ _ _ _
Releasing Zone selection (R5 shown)
key until you return to the Program Change
ESC
Monitor
Detector
Module
R05
Control
B01
Module
Releasing Applications
.
Type Code
MAN
RELEASE
MAN RELEASE
2 M 1 0 1
75