F.5: Type Codes For Output Devices; F.5.1: Overview; F.5.2: Type Codes For Control Modules - Honeywell Notifier NFS2-640/E Programming Manual

Fire alarm control panel
Hide thumbs Also See for Notifier NFS2-640/E:
Table of Contents

Advertisement

Type Codes for Output Devices
1
CO MON
CO alarm
3
ECS/MN MONITOR
MN alarm
ESC/MN SUPT
supervisory
3
ECS/MN SUPL
supervisory
ECS/MN TROUBLE
trouble
3
MON
RF GATEWAY
non-alarm
1
LED representation of a CO alarm may be performed using an ACS annunciator.
2
If ECS/MN Override is not selected in VeriFire Tools, the fire events take precedence over ESC/MN audio events.
3
This type code is not compatible with FirstCommand applications.
F.5 Type Codes for Output Devices
F.5.1 Overview
This section provides Type Codes for control modules and NACs. For instructions on programming
Type Codes, refer to "Modify or Delete a Point (2=point)" on page 19.
F.5.2 Type Codes for Control Modules
A comprehensive list of control module Type Codes, which you can select to change the function of
an control module point.
Type Code
Silenceable (Y/N) Configuration
CONTROL
Y
RELAY
Y
BELL CIRCUIT
Y
STROBE CKT
Y
HORN CIRCUIT
Y
AUDIBLE CKT
Y
SPEAKER
Y
ISOLATED NAC
Y
ISOLATED SPK
Y
REL END BELL
N
blank
Y
REL CKT ULC*
N
RELEASE CKT*
N
RELEA.FORM C*
N
REL AUDIBLE
Y
NONRESET CTL
N
TELEPHONE
N
INSTANT RELE
N
ALARMS PEND.
N
CONTROL NAC
Y
GEN ALARM
N
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Table F.2 Type Codes for Monitor Modules (2 of 2)
Y
No LED will light. Special Function Zone FC
and the sixth CBE zone will activate (sixth
CBE programmable via VeriFire Tools.)
Y
Does not light any LEDs, overrides existing
2
fire event
, shuts off silenceable outputs
and all fire activated strobes and activates
CBE.
N
Lights supervisory LED and activates CBE.
Y
Lights supervisory LED and activates CBE.
N
Indicates trouble on a Mass Notification
device.
N
Activates CBE
Table F.3 Control Module Type Codes (1 of 2)
Device Function
NAC
Supervised NAC for notification appliance
Form-C relay
Relay output
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC for notification appliance, used with audio isolators. Activates even if
there is a short on its NAC circuit. For ULC installations only.
NAC
Supervised NAC for speaker circuits, used with audio isolators. Activates even if there
is a short on its audio circuit. For ULC installations only.
NAC
Supervised NAC for notification appliance
NAC
Supervised NAC (for use when no other Type Code applies)
NAC
Releasing Circuit, power-limited, supervised for opens, shorts and ground faults
(always non-silenceable)
NAC
Releasing circuit, nonpower-limited, supervised for opens and ground faults
Form-C Relay
Relay output, contacts operate upon release
NAC
NAC, activated upon release
Form-C Relay and NAC
Relay output, unaffected by "System Reset" command
NAC
Standard Telephone circuit
NAC
NAC, short = normal; supervised for open circuits and ground faults. Always non-
silenceable and switch-inhibited.
NAC
Output that will activate upon receipt of an alarm condition, and remain in the alarm
state until all alarms have been acknowledged. It is programmed as "switch inhibit".
NAC
Supervised NAC
NAC
Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) configured as a
Municipal Box Transmitter for NFPA 72 Auxiliary Fire Alarm Systems applications. This
Type ID can also be used for general alarm activation. It is programmed as "switch
inhibit".
Monitors conventional CO detector
Monitors mass notification devices
Monitors mass notification devices
Monitors mass notification devices.
Monitors mass notification devices. Will generate a
trouble condition for both open and short conditions.
Provides communication between wireless device and
the fire panel.
Type Codes
115