How to Program a Releasing Zone
Detector
CBE list = Z01 ZR1
A listing of each Cross Zone option and the conditions required to activate the Releasing Zone,
according to the example shown above.
Cross Zone
Selection (Cross=)
Cross=N
Cross=Y
Cross=Z
Cross=H
Select a time for the Releasing Zone Delay Timer (refer to"Programming a Delay Timer" on page
61.)
To Program
Cross Zones
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Smoke
Heat
Detector
2D104
2D102
Figure A.9 Illustrated Example of Cross Zone Programming
Condition(s) Required to Activate the Releasing zone
An alarm from any detector or module activates the releasing circuit.
An alarm from any two detectors or modules activates the releasing
circuit.
An alarm from two detectors or modules mapped to different Software
Zones, but mapped to the same Releasing Zone.
• An alarm from 2D101 and 2D103
• An alarm from 2D102 and 2D104
• An alarm from 2D101 and 2D104
• An alarm from 2D102 and 2D103
The two detectors listed in each set above are each mapped to different
zones, but both list ZR1 in their CBE.
Activation of heat detector 2D104 and one smoke detector (2D101,
21D102, or 2D103) or a module mapped to the same releasing zone.
Do this
Type N, Y, Z, or H in the CROSS= field, or press the
or
Software
Zone Z01
CBE list = Z02 ZR1
Smoke
Software
Detector
Zone Z02
2D103
Releasing
Zone ZR1
REL
CBE list = ZR1
B03
, until N, Y, Z or H appears in the that field.
Releasing Applications
Smoke
Detector
2D101
CBE list = Z01 ZR1
or
keys,
NEXT
PREVIOUS
71