FlashScan Poll

Utility Option
IP ACCESS
DCC Mode
To select utility options, follow these steps:
1.
Using the arrow keys, move the blinking cursor to a selection.
2.
Press the
- Local Control
- *, 1, 2, 3, 4, 5 (TBL Reminder)
- 0, 1, or 2 (IP ACCESS)
- DCC Mode
3.
When finished making selections, press the
normal operation.
2.6 FlashScan Poll
Program Change
Password
This menu allows the selection of CLIP (Classic Loop Interface Protocol) or FlashScan detectors
and modules for each loop. Once this screen is accessed, the cursor will be positioned underneath
the Loop #1 Detector selection, blinking the currently selected protocol type. The default selections
are shown in the above figure. This indicates that both Loop #1 and Loop #2 detectors and modules
are selected to use CLIP devices. If FlashScan devices are to be employed, change the blinking
cursor by pressing the Y key or toggle it by using the
have been made to the detectors and modules of both loops, press the
panel will reset.
Most FlashScan devices can be programmed to run in either CLIP or FlashScan mode. Observe one
of the following three options when using FlashScan devices:
Option 1
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
Table 2.35 Utility Program Options (2 of 2)
Description
Note: Use of this option is subject to local AHJ approval.
This option allows the programmer to choose one of three options for Wide Area Network
(WAN) communication. Acceptance of commands, downloads and programming from over the
WAN can be enabled, disabled or timed.
Select IP ACCESS as follows:
• Select 0 to disable IP access
• Select 1 to enable IP access
• Select 2 to enable IP access for two hours.
Note that enabling IP ACCESS allows downloads over a local area network (LAN) or the
internet (Wide Area Network - WAN) using VeriFire Tools through a Noti•Fire•Net(NFN) Web
Server (NWS), or a wide-area enabled NCS through a PC version of NFN Gateway. Always
verify system operation after programming changes are made in this manner.
This option allows the programmer to select whether this panel will participate in DCC (Display
and Control Center) functions. Select Y for participation, N for no participation.
NOTE: For Mass Notification applications, DCC participation should be disabled.
or
key to select
NEXT
PREVIOUS
From the "Program Change Selection" screen, press the 4 key to access the
"FlashScan Poll" selection screen as shown below:
F L A S H S C A N
Program all modules and detectors on an SLC as FlashScan.
(In the "FlashScan Poll" screen, enter Y for DET and Y for MOD. It is possible to
have up to 159 FlashScan modules and 159 FlashScan detectors on this SLC.)
key three times to return the control panel to
ESC
L 1 D E T
L 1 M O D
L 2 D E T
N
N
or
key. After the selections
PREVIOUS
NEXT
ENTER
Programming
L 2 M O D
N
N
key, at which time the
49