Releasing Applications
A.2.3 Using Cross Zones
Purpose of Cross Zones
Using Cross Zones lets you program the control panel to activate a Releasing Zone and any output
mapped to the Releasing Zone only after a predetermined sequence of events occurs. (If not using
Cross Zones, set CROSS= N.)
NOTE: Only the first Software Zone (Z01-Z99) listed in the zone map is used to determine
Cross=Z.
A summary of the types of Cross Zones and the conditions for activating a Releasing Zone:
Type
Y
Z
H
NOTE: When in alarm, Special Zones R0-R9 appear in the CBE list as ZR00-ZR09. For
example, R5 appears in the CBE list as ZR05.
How Cross Zones Work
Below is an illustrated example of how Cross Zones work, using five Cross Zone selections (four
detectors and a NAC mapped to Releasing Zone R1):
70
Activates when
Two or more detectors or modules are alarmed that are mapped to one of the ten Releasing Zones
(R0-R9).
Two or more detectors or modules are alarmed that are mapped to two different software zones
and mapped to one of the ten Releasing Zones (R0-R9).
At least one smoke detector or module mapped to one of the ten Releasing Zones (R0-R9) is
alarmed and at least one heat detector mapped to the same Releasing Zone (R0-R9) is alarmed.
P R O G R M S M O K E ( P H O T O ) D E T E C T O R A D D R 2 D 1 0 1
CBE list = 01 R1
P R O G R M S M O K E ( P H O T O ) D E T E C T O R A D D R 2 D 1 0 2
CBE list = 01 R1
P R O G R M S M O K E ( P H O T O ) D E T E C T O R A D D R 2 D 1 0 3
CBE list = 02 R1
P R O G R M H E A T ( A N A L O G ) D E T E C T O R A D D R 2 D 1 0 4
CBE list = 02 R1
P R O G R M R E L E A S E C K T
CBE list = R1
0 1 R 1 _ _ _ _ _ _ A 8 P 8 * * 2 D 1 0 1
0 1 R 1 _ _ _ _ _ _ A 8 P 8 * * 2 D 1 0 2
0 2 R 1 _ _ _ _ _ _ A 8 P 8 * * 2 D 1 0 3
0 2 R 1 _ _ _ _ _ _
F R O N T H A L L W A Y N O . 3
R 1 _ _ _ _ _ _ _ _
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
How to Program a Releasing Zone
* * 2 D 1 0 4
I * *
B 0 3