How to Program a Releasing Zone
Example
An AHJ Abort Switch and a Delay Timer programmed to Releasing Zone R05:
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14
P R G R E L E A S E F U N C T I O N R E L E A S E C O N T R O L
D E L A Y = 6 0 A B O R T = A H J C R O S S = N S O K = 0 0 0 0
Program selections for Releasing Zone R05
Delay=60 sec.
0 sec.
45 sec.
45 sec.
Alarm
Press and hold
the Abort Switch
Release the Abort Switch and control
panel restores the programmed value the
Delay Timer (60 sec.) and counts down
Figure A.8 AHJ Abort Switch Example
Total time from alarm initiation to release:
45 + 30 + 60 = 135 seconds
60 sec.
75 sec.
30 sec.
60 sec.
When the Delay Timer
expires, the control panel
activates Releasing
Zone outputs
Releasing Applications
R 0 5
135 sec.