Releasing Applications
ABORT SWITCH
The following contains information needed to program an Abort Switch for a monitor module
Description
A monitor module, connected to a UL-listed abort station (such as the Notifier NBG-12LRA), that
you use as an abort switch for a Releasing Zone. You can program multiple monitor modules with
the
ABORT SWITCH
conventional zone.
Programming
1.
Select a monitor module to use as an Abort Switch (refer to "Modify or Delete a Point
(2=point)" on page 19).
2.
Select the
3.
Select the Releasing Zone (R0-R9) for your releasing application.
4.
Press the enter key to save, then press the esc key until you return to the Program Change
screen.
5.
Select the type of Abort Switch for your releasing application (refer to "Abort Switches" on
page 62).
Example
A programming example of a monitor module programmed as an Abort Switch for Releasing Zone
R5.
74
Type Code
Type Code that work like multiple conventional abort switches on a
Type Code.
ABORT SWITCH
P R O G R M A B O R T _ S W I T C H M O D U L E A D D R 2 M 1 0 1
SYSTEM
SYSTEM
NORMAL
ACTIVATED
Type Code
ABORT SWITCH
NBG-12LRA
station with
Abort Switch
Figure A.10 Monitor Module Configured as an Abort Switch
How to Program a Releasing Zone
Type Code selection:
R 1 _ _ _ _ _ _ _ _
Releasing Zone selection (R1 shown)
Monitor
Module
R05
B01
NFS2-640/E Programming Manual — P/N 52742:L2 7/17/14